Why a checklist is only ever a starting point
A printed checklist is useful for structuring a walk-through, but it is not itself a fire risk assessment, and treating it as one is one of the more common ways landlords end up with a document that will not survive contact with an enforcement officer, an insurer's loss adjuster or a lender's solicitor. The Fire Safety Order 2005 requires a 'suitable and sufficient' assessment carried out or reviewed by a competent person, which means judgement applied to the specific building, not boxes ticked against a template downloaded from the internet. What follows is the structure a competent assessor actually uses, in the order they typically move through a building, together with the specific items within each area that most often go wrong on London stock.
- Identify the fire hazards present in and around the building
- Identify who could be harmed and how, including vulnerable residents
- Evaluate the risk and decide whether existing precautions are adequate
- Record the significant findings, the action plan, and any training given
- Review the assessment regularly and after any material change
1. Escape routes
The single most important element of any assessment. Everything else — doors, alarms, lighting — exists to keep an escape route usable for long enough for everyone to get out. An assessor walks every route from the furthest habitable room to the final exit, not just the ground floor, and checks it against the travel distance and occupancy guidance in Approved Document B and BS 9999. In a converted Victorian terrace split into flats this often means a single staircase serving every floor with no protected lobby, which changes the standard of protection that stairway needs to justify carrying the whole building's escape. In a 1960s purpose-built block it more often means checking that decades of resident alterations, satellite dishes and bike storage have not quietly narrowed a corridor that was compliant when the block was built.
- Can every occupant reach a final exit without passing through a higher-risk room such as a kitchen, plant room or store?
- Are corridors, stairwells and lobbies clear of storage, bikes, buggies, mobility scooters and combustible clutter?
- Do final exit doors open without a key, code or restricted access from the inside at all times?
- Are travel distances reasonable for the occupancy type and consistent with the alarm coverage installed?
- Where there is a single stair, is the standard of protection to that stair — doors, walls, ventilation — high enough to justify it carrying the whole building?
- Are external escape routes such as balconies, deck-access walkways and external stairs free of obstruction and structurally sound?
Escape route quick checks a landlord can do before we arrive
- Walk the full route from top floor to streetNot just the ground floor — check every landing
- Remove any bikes, buggies or bins from corridors and stairsThis is the single most common finding we record
- Confirm final exit doors open freely from the insideNo thumb-turn locks that residents leave locked overnight
- Check nothing has been stored against a fire door
2. Fire doors and compartmentation
Compartmentation is what buys occupants time to escape and firefighters time to work, and it is also the thing most often quietly destroyed over the years by cabling contractors, plumbers, satellite installers and residents replacing their own front doors without building control sign-off. An assessor checks both the physical door and the wall, floor and ceiling construction around it, because a perfect fire door in a wall with an unfilled service penetration next to it offers very little real protection. On London blocks we regularly find riser cupboards where a decade of different contractors have each drilled a new hole for cabling or pipework and none of them made good the fire-stopping afterwards.
- Do fire doors self-close fully into the frame from any open angle, on the first attempt?
- Are intumescent strips and cold smoke seals present, continuous and undamaged around the full perimeter?
- Are gaps around the door leaf — head, sides and threshold — consistent and within the 3mm/8mm tolerances referenced in BS 8214?
- Is the door and frame certified — look for a coloured plug or certification label on the door edge?
- Have service penetrations for cabling, pipework or vents through fire-separating walls and ceilings been properly fire-stopped with a certified system?
- Are communal fire doors held open illegally with wedges, chains or fire extinguishers?